Technical data sheet
01MT-5..
Average Temperature Sensor
The Pt1000 version is supplied with one
continuous sensing element across the whole
length of the probe to ensure optimum accuracy
and eliminate air stratification problems.
NTC and Ni1000 are industry standard multi-point
sensing elements.
Type Overview
Tyyppi
Output signal
Pt1000
Anturiputken pituus
01MT-5B4
01MT-5B5
01MT-5E4
01MT-5E5
01MT-5L4
01MT-5L5
01MT-5M4
01MT-5M5
01MT-5Q4
01MT-5Q5
10 ft [3 m]
20 ft [6 m]
10 ft [3 m]
20 ft [6 m]
10 ft [3 m]
20 ft [6 m]
10 ft [3 m]
20 ft [6 m]
10 ft [3 m]
20 ft [6 m]
Pt1000
Ni1000 (JCI)
Ni1000 (JCI)
NTC10k (10k2)
NTC10k (10k2)
NTC10k3 (Precon)
NTC10k3 (Precon)
NTC20k
NTC20k
Technical Data
Electrical Data Electrical connection
Cable entry
Removable spring loaded terminal block max. 2.5
mm²
Cable gland with strain relief Ø6...8 mm (1/2" NPT
conduit adapter included)
Functional Data
Output signal passive temperature
Pt1000
Ni1000 (JCI)
NTC10k (10k2)
NTC10k3 (Precon)
NTC20k
Application
air
Measuring Data
Measuring values
Temperature
Measuring range temperature
Pt.., Ni.. : -30...160°F [-35...70°C]
NTC.. : -30...120°F [0...50°C]
Accuracy temperature passive
Measuring current
Passive Sensors depending on used type
Pt.. : ±0.5°F @ 32°F [±0.3°C @ 0°C]
Ni.. : ±0.7°F @ 32°F [±0.4°C @ 0°C]
NTC.. : ±0.35°F @ 77°F [±0.2°C @ 25°C]
Pt1000: <0.3 mA @ 32°F [0°C]
Ni1000 (JCI): <5 mA @ 21°C [70°F]
NTC10k2: <2 mA @ 77°F [25°C]
NTC10k3: <2.7 mA @ 77°F [25°C]
NTC20k: <0.5 mA @ 77°F [25°C]
Time constant τ (63%) in air duct
typical 100 s @ 0 m/s
Materials
Cable gland
PA6, black
www.belimo.com
01MT-5.. • en-us • 2020-10-01 • Subject to change